Voltage Regulation < ±1%
Can Be Use In Parallel Operation
Wider Sensing Input 90~520 VAC
Model NO. EA440-T Sensing Input Terminal 0-110V = 90~150V Terminal 0-220V = 175~260V Terminal 0-380V = 350~520V Power Input Voltage 100~264 VAC single phase Output Voltage Max. 90 VDC at 207 VAC Current Continuous 4A, Intermittent 10A for 10 sec. Resistance Min. 15 Ohm Voltage Regulation 5 VAC External Volts Adjustment ±8% with 1 K Ohm 1 watt trimmer Unit Power Dissipation Max. 12 watt Thermal Drift 0.05% per °C change in AVR ambient Under Frequency Protection U/F potentiometer 45~60 Hz Analogue Input Max. input ±5 VDC Sensitivity 1V for 5% generator volts Input resistance 1 K Ohm DROOP Input Burden 10 Ohm Max. sensitivity 0.07A for 5% droop (PF=0) Max. input 0.33A Environment Operating Temperature : -40~60 °C Storage Temperature : -40~85 °C Relative Humidity : Maximum 95% Vibration : 1.5G @ 5~30 Hz / 5.0G @ 30~500 Hz AVR Controls Functions VOLT : Voltage Adjustment STAB : Stability Adjustment U/F : UFRO Knee Point Set DROOP : Droop Adjustment TRIM : Analogue Input Adjustment DIP : U/V Rate Set Dimensions 150.0 (L) x 135.0 (W) x 40.0 (H) mm