All Categories
Get it between 2025-03-13 to 2025-03-20. Additional 3 business days for provincial shipping.
Body Sizes and End Connection Styles (inlet x outlet): 1/2-inch x 1/2-inch NPT
Maximum Inlet Pressure: 10 psig / 0,69 bar : Emergency Inlet Pressure: 40 psi / 2.8 bar
Outlet Pressure Ranges : 9.5 to 13-inches W.C / 24 to 32 mbar
Capacity : 650,000 BTU/hr
Vent Size : 3/8 NPT screened
Fisher Type R222 Series is an Underwriters Laboratories listed regulator designed for Two-Stage LP-Gas systems. The unit is designed to reduce the outlet pressure from a first-stage regulator (usually 10 psig / 0.69 bar) to an outlet pressure of 11-inches w.c. / 27 mbar. The units compact size makes it ideal for tight fit applications. A screened drip-lip vent is oriented over the inlet in the standard configuration. Fisher second-stage regulators are painted palm green for easy identification. !!! WARNING !!! Failure to follow these instructions or to properly install and maintain this equipment could result in an explosion and/or fire causing property damage and personal injury or death. Fisher equipment must be installed, operated and maintained in accordance with Federal, state and local codes and Fisher instructions. The installation in most States must also comply with NFPA no. 54 and 58 standards. Only Personnel trained in the proper procedures, codes, standards and regulations of the LP-gas industry should install and service this equipment. BUYER AGREES THAT RESPONSIBILITY FOR PROPER SELECTION, INSTALLATION, USE AND MAINTENANCE OF ANY PRODUCT REMAINS SOLELY WITH THE PURCHASER AND END-USER. BUYER AGREES TO COMPLY WITH THE ABOVE WARNING AND ALL INSTRUCTION MANUALS, BULLETINS AND INSTALLATION GUIDES ASSOCIATED WITH THIS PRODUCT.