All Categories
This CR Magnetics CR4511 series current transducer combines a solid-core current transformer and signal conditioner, and is suitable for use in industrial automation systems. The transducer provides true root-mean-square (RMS) measurement for distorted voltage waveforms, with an accuracy of 0.5% full scale (FS) and a response time of 250 ms (10-90% step change). Mounting options include DIN rail or panel. This voltage transducer is Underwriters Laboratories (UR) Recognized and Conformité Européenne (CE) certified for quality assurance. It is suitable for monitoring variable-frequency drive (VFD) and silicone control rectifier (SCR) loads and other "noisy" loads that produce distorted waveforms. Specifications Signal Output 0-10 VDC Frequency Range 20-5,000 Hz Insulation Voltage 2,500 VDC Output Loading 2 K ohm minimum Operating Temperature 0 C to 50 C CR Magnetics manufactures electrical sensors, indicators, and displays. The company, founded in 2004, is headquartered in Saint Louis, MO.